RGEI Gateway features
What the RGEI Gateway does, as of firmware 1.4.0 (13 October 2026).
Overview
The gateway is a small computer with a touchscreen. It is located at a customer site, shows the site's power figures, and passes encrypted CSIP-AUS export-limit controls through to the site. Each unit reports to a cloud service, so the operator can see its status, change some settings and roll out firmware from the admin console.
Hardware and screens
- 2.8-inch ILI9341 colour touchscreen, landscape.
- Four screens: clock, CSIP control, site (Victron / Fronius) and about.
- Auto-rotate cycles the screens every 30 seconds. It can be turned on or off on the unit's page or from the cloud.
- Swipe up for CSIP control, swipe down for the clock.
- Screen backlight is adjustable from the unit's page.
Each unit has its own web page
- Served from the unit's own IP address on the local network, behind a login.
- Device Status: firmware version, IP, MAC, serial number, Wi-Fi network and signal, uptime and licence state.
- Settings: Auto-rotate, Debug logging, Display backlight, Gateway Server URL, GX Address, Change Web Password, Connect to New WiFi and Factory Reset.
- CSIP Control and Site (Victron GX) panels showing the live values.
- Debug Log panel, with a Clear button.
Setup and networking
- A setup hotspot, with a QR code on the screen to join it from a phone.
- The serial number is the Wi-Fi MAC address without colons, in capitals. It identifies the unit in the cloud and in licensing.
- The Gateway Server URL is set on the unit's page, so a unit can point at the live or staging cloud.
Cloud connection
- Telemetry is posted encrypted every 30 seconds: solar, grid, load, battery state of charge and power, Wi-Fi signal and firmware version. The unit also sends a snapshot of what its own page shows.
- The unit polls the cloud for status every 15 seconds. Only outbound HTTPS is used, so no ports need opening on site.
- Telemetry is stored with the unit's record, so the cloud shows the last seen time and the latest readings.
Cloud admin console
- List of every licensed unit: status, serial, name and site, ICP or NMI, network operator, last seen, solar, grid, Wi-Fi, control state and firmware.
- Per-unit page: device status, settings, CSIP control, site readings, an approximate live view of the screen and firmware.
- Licence actions per unit: edit, renew, CSIP report, sticker and revoke.
- Reports: CSIP report for all sites and a licence expiry report.
- Network operators, each with a login to the operator page, which shows only that operator's sites.
- Units waiting for a licence are listed, so new units can be added quickly.
Remote settings
- From the cloud, the operator can change Auto-rotate and Debug logging.
- A change is queued, and the unit picks it up on its next status check, within about 15 seconds.
- Each change is applied once. The unit reports back, and the page shows "applied" once it has.
CSIP and DER control
- The unit shows the current CSIP mode, export limit, active control and when it ends.
- Control state comes from the cloud status feed and is shown on the screen and on the unit's page.
- Units without a licence show "Not licensed" and do not receive control.
Victron GX site data
- The unit reads the GX over the local network, using MQTT, once a GX Address is set.
- Shows site solar, grid (import positive, export negative), load, battery power and state of charge, and the GX export limit setting.
Licensing
- A unit must be licensed before it sends control data or receives firmware. Unlicensed units are refused.
- Licences can run for a set number of months, or have no end date. Expiry is shown on the admin page.
- A licence can be renewed, or revoked to switch a unit off.
Firmware updates
- Updates are downloaded over the internet from the cloud, and each one is checked against its checksum before it is installed.
- Units check for updates every 6 hours. The cloud can also prompt an immediate check, at most every 10 minutes.
- Releases are published from a build on the PC. Each release has a version and notes.
- Rollout can go to chosen units only (try one first), to every licensed unit, or be paused. A release goes to nobody until units are chosen.
- Only licensed units receive a release. The unit shows "NO UPDATE" when there isn't one.
- Every registered unit has remote access to it for updates and configuration.